The XM-320 module (catalog number: 1440-TPS02-01RB) is designed to measure turbine supervisory position metrics, including axial position (thrust), valve position, differential expansion, and case expansion.
Specifications
Inputs
- Channels: 2 channels
-
Signal Types:
- Eddy current transducer signals
- Linear variable differential transformer (LVDT)
- Voltage signals from any position measurement sensor
- Transducer Power: Isolated 24V, configurable for +24V or -24V wiring
- Voltage Range: Selectable in software between -24V and +24V
- Sensitivity: User-configurable in software
- Input Impedance: > 100 kΩ
Outputs
-
4…20mA Outputs:
- Two isolated outputs
- Max load: 600 Ω
- Buffered Outputs: Two outputs (one per channel)
Indicators
- Module Status: Red/green
- Network Status: Red/green
- Channel 1 Status: Yellow/red
- Channel 2 Status: Yellow/red
- Setpoint Multiplier Status: Yellow
- Relay Status: Red
Communication
-
DeviceNet Network:
- Standard DeviceNet protocol for all functions (module power provided independently)
- EDS file available for support with most DeviceNet-compliant systems
- Automatic communication rate setting: 125, 250, or 500 Kbps
- Configurable I/O Poll Response message for space optimization within scanner input tables:
- Selectable poll response assembly
- Selectable poll response size (bytes)
-
Serial Communication:
- RS-232 via mini-connector or terminal base unit
- Fixed communication rate of 19.2 Kbps
- Local configuration via Serial Configuration utility
Measurement Modes
- Normal: Two independent channels
- Head-to-head
- Radial cancel
Delta Time Buffer
- Number of Records: 2048
- Delta Time Interval: 1 to 3600 seconds
- Trigger Mode: Triggered by relay activation or a DeviceNet command from a controller or host
Alarms
- Number of Alarms: Two alarm and danger pairs
-
Operators:
- Greater than
- Less than
- Inside range
- Outside range
- Hysteresis: User-configurable in software
-
Startup Inhibit/Setpoint Multiplication:
- Period: 0 to 1092 minutes, adjustable in 0.1-minute increments
- Inhibit/multiplication function: Multiply by N (0 to 10, 0 = Disarm)
Relays
-
Number of Relays:
- Single on-board relay with two sets of DPDT contacts (2 Form C)
- Four additional relays with XM-441 expansion relay module
- Four virtual relays (status can be used by remote control systems or XM-440 master relay module)
-
On-board Relay Rating:
- Max Voltage: 125V DC, 125V AC
- Max Current: 3.5 A (derates to 2 A at 65°C / 149°F)
- Max Power: 60 W (DC), 62.5 VA (AC)
-
Failsafe Options:
- Normally energized (failsafe)
- Normally de-energized (non-fail-safe)
-
Latching Options:
- Latching
- Non-latching
- Time Delay: Adjustable from 0 to 25.5 seconds in 100 ms increments
- Logic: Single or paired AND or OR logic for alarm triggers
-
Reset Options:
- Local reset switch on top of module
- Remote reset switch via terminal base
- Digital reset command via serial or DeviceNet interface
Configuration
-
Non-volatile Configuration:
- Configuration is stored in non-volatile memory and is loaded on power-up
- Configuration can be deleted only by module reset via serial or DeviceNet interface
Power
- Module Power: 24V DC
-
Power Consumption:
- Max: 200 mA
- Typical: 165 mA
-
Heat Production:
- Max: 5.28 W (18 BTU/hr)
- Typical: 3.96 W (13.5 BTU/hr)
Physical Specifications
- Terminal Base: 1440-TB-B
- Dimensions (H x W x D): 97 x 94 x 94 mm (3.8 x 3.7 x 3.7 in.)
Quick Quotes | Receive price & availability FAST from our dedicated customer service team. |
---|---|
Delivery | Expedited, Freight, And International Shipping Available. |
Condition | 100% New with Original Package |
Payment | We accept American Express, Discover, MasterCard, PayPal, and Visa. Our site is secured by RapidSSL. |
Shipping Port | ShangHai, Xiamen |
Warranty | 12 Months |
Q: Is Our Pricing Competitive? |
A: Yes, we collaborate with over 50 countries worldwide. As a top supplier in China, we offer significant discounts based on market trends. |
Q: What Is the Warranty Period? |
A: All our new and original products come with a standard one-year warranty. |
Q: What Payment Methods Do We Accept? |
A: We require 100% T/T (Telegraphic Transfer) payment before shipping. For items with a lead time, a 30% deposit is needed upfront, and the remaining 70% is due before shipping. If you have a representative in China, you can arrange an RMB transfer through them. |
Q: What Shipping Methods Do We Use? |
A: We primarily use FedEx, DHL, UPS, and BRE for shipping. If you have an account with any of these carriers, you can handle shipping directly. We also offer free shipping to China-based freight forwarders. |
Q: What Is Our Delivery Time? |
A: Delivery usually takes 1-3 days after receiving the initial payment. For items with a lead time, shipping will occur according to the specified schedule. |
Q: How Do We Package the Goods? |
A: We ensure safe packaging with multiple layers of protection. Products are first placed in their original boxes and sealed with labels. A layer of bubble wrap is then added for collision protection during transit. Finally, the items are packed securely in durable boxes. |
Q: How Can Customers Contact Us and Request a Quote? |
A: You can reach out to us via email, WhatsApp, WeChat, Skype, or your preferred communication platform. Contact us with your needs, and we'll provide a prompt, customized quote. |
Recently Viewed
Express Shipping
Rapid delivery for your urgent requirements.
Extensive Inventory
Large stock for immediate dispatch.
Quality Assurance
Authentic, top-grade PLC & DCS components.
Global Service
Supporting clients worldwide with dependable service.